The NEW Series DPM Particulate Monitor combines with the PMS Particulate Sensor to provide a basic baghouse and cartridge filter leak detector designed for general maintenance planning and process protection. It is easy to use and reliable. Leakage is gauged in real-time, on-the-spot, without prior baseline data and without signal tuning. An alarm point is set by simply moving an indicator up and down the gauge with the convenient, lockable key pad. The digital readout in absolute units ensures correct interpretation of the readings and provides accurate historical comparisons. The DPM Control Unit is housed in a rugged cast aluminum enclosure, while an LCD displays particulate levels in bar-graph and digital forms.• Inputs: From PMS Sensor. • Output Ratings: Alarm Relays: 2 Form A (SPST) rated 5A @ 240V res. (must provide an 8A [maximum] fuse in series with relay load); Analog: 4 to 20 mA (Option RC). • Power Requirements: 115 VAC 50/60 Hz, 230 VAC 50/60 Hz, or 24 VDC. • Power Consumption: 6 Watts Max. • Accuracy: Standard: ±5% of range; Optional: ±1% of range. • Display: LCD. • Display Resolution: Standard: 5 pA; Optional: 0.5 pA. • Memory Backup: For set point storage only. • Temperature Limits: -13 to 160°F (-25 to 70°C). • Weight: 4.5 lbs (2.0 kg). • Enclosure: Cast aluminum, weatherproof, NEMA 4X. • Loop Power Supply (Isolated): 17 VDC loop supply provided by DPM control unit for PMS sensor. • Agency Approvals: Standard, Ordinary/General Purpose Locations (CE and CSA) or Optional, Class I, II, III, Div. I & II, All Groups (Intrinsically Safe- CSA).